Fire safety for small blocks of flats: a checklist for directors
Quick answer
However small the block, you still need a suitable and sufficient fire risk assessment of the common parts, fire safety measures kept in working order, clear escape routes, and fire safety instructions and fire door information for every resident at least every 12 months. The 3-monthly and yearly fire door check duties only apply to buildings over 11 metres.
If you're a director of a residents' management company, right to manage company or apartment management company, or a freeholder, your company is likely to be the “responsible person” for fire safety in your block. The duties apply however small the block, and whether or not the directors are volunteers. This checklist sets out what the law expects, with the technical detail you'll need when you speak to fire risk assessors, contractors and the fire and rescue authority.
Are you the responsible person?
Under article 3 of the Regulatory Reform (Fire Safety) Order 2005, the responsible person is whoever has control of the premises, which for a block of flats usually means the freeholder or the management company. In a block of flats, the Order covers the common parts, the building's structure and external walls, and the entrance doors of flats that open onto the common parts. The Fire Safety Act 2021 made this clear.
Where more than one person has duties, for example a freeholder and a right to manage company, each must co-operate and co-ordinate with the others. Since 1 October 2023, every responsible person must also share their name and a UK address with residents and with other responsible persons.
Fire risk assessment: what “suitable and sufficient” means
Article 9 of the Order requires a suitable and sufficient fire risk assessment. For blocks of flats, assessors commonly follow PAS 79-2:2020 (fire risk assessment for housing) and the Local Government Association's guide, Fire safety in purpose-built blocks of flats, which describes four types of assessment:
- Type 1: common parts, non-destructive, including a sample of flat entrance doors. Normally enough for most purpose-built blocks.
- Type 2: common parts, destructive, for example opening up construction to check compartmentation where serious defects are suspected.
- Type 3: common parts and flats, non-destructive.
- Type 4: common parts and flats, destructive.
Since 1 October 2023, you must record the whole fire risk assessment and your fire safety arrangements, including the name of the person who carried it out, and their organisation if they have one. Keep it under review, and review it whenever there's reason to think it's no longer valid, for example after building work or a fire.
Fire safety checklist for small blocks of flats
- Get a fire risk assessment of the common parts. It must be suitable and sufficient, carried out by a competent person, recorded in full, and kept under review. Look for an assessor on a recognised register or third-party certification scheme.
- Act on the findings. Prioritise the actions by risk, put the recommended fire precautions in place, and record when each one is closed out.
- Keep fire safety measures maintained. Fire doors and their self-closing devices, emergency lighting, fire safety signs, and any fire alarm, smoke ventilation or dry riser must be kept in efficient working order and good repair. Typical routines: emergency lighting tested monthly and given a full-duration test once a year (BS 5266-1); any fire alarm tested weekly and serviced at least every 6 months (BS 5839-1); any dry riser visually inspected every 6 months and pressure-tested every year (BS 9990).
- Give residents fire safety instructions and fire door information: to every resident when they move in, at least every 12 months, and after any material change. Display the instructions in a conspicuous part of the common parts.
- Keep escape routes clear. Stairs, corridors and entrances must be free of combustible materials and obstructions such as rubbish, bikes, prams and furniture. Fire services warn against storing or charging e-bikes and e-scooters in common parts, because lithium-ion battery fires develop fast and produce toxic smoke.
- Check fire doors if your building is over 11 metres: communal fire doors at least every 3 months, and best endeavours to check flat entrance doors at least once a year. Check that each door closes fully onto its latch from any angle of opening, and that its seals, hinges and glazing are intact. Record each check, including failed attempts to get access.
- Co-operate and co-ordinate. If someone else controls part of the building, such as a shop on the ground floor, or there's more than one responsible person, share fire safety information and co-ordinate your arrangements.
- Use competent people. Use fire risk assessors, fire door inspectors and installers with the right training, experience and, ideally, third-party certification.
- Keep records: your fire risk assessment, fire safety arrangements, checks, servicing, repairs, and what you gave residents and when.
- Hand over properly. When directors or managing agents change, pass on the records and the dates when things are next due, so nothing is missed.
What changes with the height of your building
Height is measured from the lowest ground level next to the building to the floor of the top storey, not to the roof, using the method in Approved Document B.
- 11 metres and under: the 3-monthly and annual fire door check duties don't apply, but you must still keep fire doors working and give residents the information.
- Over 11 metres: 3-monthly communal fire door checks and annual flat entrance door checks (best endeavours). If the building has a simultaneous evacuation strategy, residential personal emergency evacuation plans also apply from 6 April 2026.
- 18 metres or more, or 7 or more storeys: the high-rise duties apply, including building plans and a secure information box for the fire and rescue service, information about the external walls, wayfinding signage, monthly checks of firefighting lifts and equipment, and residential personal emergency evacuation plans. Most of these buildings are also higher-risk buildings under the Building Safety Act 2022, with an accountable person who must register the building with the Building Safety Regulator.
How Resident Fire Safety helps
Resident Fire Safety takes care of item 4, including the section 156 information residents must be given. It produces the resident leaflet and the notice for your common parts, tailored to your evacuation strategy, keeps a flat-by-flat record of which flats have received it, and shows you when the next pack is due.
£59 per building per year, whatever the number of flats. For a 12-flat block, that's under £5 per flat a year. See pricing
This checklist is general information, not legal or fire safety advice for your building.
For a summary you can keep, download our free fire safety guide for blocks of flats.
Sources: Regulatory Reform (Fire Safety) Order 2005, Fire Safety (England) Regulations 2022, Fire Safety Act 2021, Building Safety Act 2022, section 156, The Fire Safety (Residential Evacuation Plans) (England) Regulations 2025
Common questions
What are the fire safety requirements for blocks of flats under 11 metres?
You still need a suitable and sufficient fire risk assessment, working fire safety measures, and fire safety instructions and fire door information for residents. The 3-monthly and yearly fire door check duties apply only to buildings over 11 metres.
How often should a fire risk assessment be reviewed?
The law doesn't set a fixed interval. It must be kept under review, and reviewed if there's reason to think it's no longer valid, such as after building work or a change in how the building is used.
Are directors personally responsible?
The responsible person is usually the company that controls the building, but directors should make sure the company meets its fire safety duties. Get legal advice if you're unsure about your position.
What type of fire risk assessment does a small block of flats need?
For most purpose-built blocks, the Local Government Association's guide says a Type 1 assessment (common parts, non-destructive) is normally enough. A more intrusive type may be needed if there's reason to suspect serious defects in compartmentation, for example after alterations, or where the history of the building is unknown.
Do we need a fire alarm in the common parts?
Not usually in a purpose-built block with a stay put strategy, because a communal alarm could cause everyone to leave when there's no need, and false alarms undermine the strategy. Each flat should have its own smoke alarm. Your fire risk assessment will say what your building needs.